Trades & DIY

Pipe Sizing & Flow Calculator

Enter your design flow rate to find the smallest standard UK pipe that stays under your target water velocity.

Recommended pipe
22mm copper
Velocity in that pipe
0.94 m/s
Flow
1.080 m³/h
SizeInternal Ø (mm)Velocity (m/s)OK?
15mm13.62.07✗
22mm20.20.94✓
28mm26.20.56✓
35mm32.60.36✓

Understanding the continuity equation

Water velocity is calculated using the continuity relationship Q = A × v. Q is volumetric flow in cubic metres per second, A is the internal cross-sectional area in square metres, and v is mean velocity in metres per second. Rearranging gives v = Q ÷ A. For a circular bore, A = π × (internal diameter ÷ 2)². The internal diameter matters because the wall and any insert take up space: a nominal 15 mm pipe does not provide a 15 mm clear passage.

Convert litres per minute to cubic metres per second by dividing by 60,000. Convert a bore measured in millimetres to metres by dividing by 1,000. Combining these conversions avoids mixing incompatible units. The calculator checks each listed pipe and recommends the smallest one at or below your chosen target velocity. If even the largest listed size fails, the warning means you need to investigate a larger pipe or a lower design flow, not that the largest option is adequate.

Worked copper sizing example

At 18 L/min, Q is 0.0003 m³/s. The listed 15 mm copper bore is 13.6 mm, giving an area of approximately 0.0001453 m² and a velocity of 2.07 m/s. The listed 22 mm copper bore is 20.2 mm: its area is approximately 0.0003205 m² and its velocity is 0.94 m/s. With a 1.5 m/s target, 22 mm is the first suitable size in the table. At a stricter 1.0 m/s target it still passes, but the actual system must also have enough pressure to deliver that flow.

Copper dimensions, wall thickness and Table X/Y

BS EN 1057 concerns seamless round copper tubes for water and gas in sanitary and heating applications. It covers product requirements; it is not a guarantee that a velocity-only calculation designs a compliant installation. Familiar Table X and Table Y descriptions refer to different wall schedules used in UK copper selection. Internal diameter follows outside diameter minus twice the wall thickness. A heavier-wall tube therefore has less flow area even where its nominal outside size is unchanged.

For illustration, a 15 mm outside diameter with a 0.7 mm wall has a 13.6 mm bore, while a 1.0 mm wall has a 13.0 mm bore. At 18 L/min, these produce approximately 2.07 and 2.26 m/s respectively. Those examples explain the geometry; they are not a complete certified Table X/Y comparison. This calculator uses the fixed bores shown in its reference table, rather than selecting a wall schedule. Confirm the actual dimensions in the tube manufacturer's datasheet for the product being installed.

Plastic pipe and support inserts can reduce the usable bore further. The listed PEX dimensions are typical assumptions, not a universal specification. Fittings, valves and appliance connections may have smaller passages than the straight pipe. A recommendation based on the pipe alone should therefore be checked against the entire assembly and the supplier's flow information.

Choosing a velocity target

The available 1.0, 1.5 and 2.0 m/s settings are planning targets. Lower velocities can help limit flow noise and friction losses, especially near bedrooms or in noise-sensitive heating circuits. A cold-main supply may tolerate a different target from a continuously circulating heating loop. Temperature, copper water chemistry, bends and operating hours also matter when assessing erosion risk. Do not treat 2.0 m/s as a universal safe limit or 1.5 m/s as a mandatory standard for every system.

Velocity does not establish pressure drop. Long runs, elbows, tees, filters and partially closed valves consume available head. A larger pipe often reduces friction, but a full design needs pipe length, roughness, fitting losses and static height. Heating calculations also need the heat load and flow/return temperature difference to determine required circulation. This tool accepts an already chosen design flow; it does not calculate that heat-load requirement or pump duty.

Practical sizing questions

Why does doubling flow not require twice the diameter?

At a fixed velocity, required area doubles with flow, while diameter scales with the square root of area. Doubling diameter gives four times the circular area. This explains why the next nominal pipe size can make a substantial difference to velocity.

Can I use this for gas, steam or compressed air?

Not as a design calculation. Compressible fluids change density and volume along a system, and gas installations have additional safety requirements. The displayed calculation is a simple incompressible-water estimate.

What should I check before ordering pipe?

Confirm peak simultaneous demand, actual bore, available pressure, route length and fitting losses. Check installation requirements with a qualified plumber or designer. Keep a record of the assumptions alongside the estimate so that changing a tap, pump or pipe material does not silently invalidate the selection.

The formula

Velocity is flow divided by the pipe's internal cross-sectional area: v = Q ÷ A, where A = π × (ID ÷ 2)².

Flow in L/min is converted to m³/s by dividing by 60,000, and the internal diameter in mm is converted to metres. For example 18 L/min through 15mm copper (13.6mm ID): 0.0003 ÷ (π × 0.0068²) ≈ 2.07 m/s — too fast, so 22mm is recommended at ≈0.94 m/s.

Velocity targets used by this estimate

The selectable 1.0, 1.5 and 2.0 m/s values are planning targets, not universal regulatory limits. Lower velocities can help reduce noise and friction. Suitability depends on the system, temperature, fittings and water conditions.

Always check the available pressure and pressure drop across the whole run, along with product instructions and applicable design guidance. This tool only checks velocity.

Plastic pipe has a thicker wall than copper of the same nominal size, so its internal bore is smaller and velocity is higher for the same flow. PEX internal diameters vary by manufacturer and whether a pipe insert is used; values here are typical.

Standard UK pipe internal diameters

Nominal sizeCopper ID (mm)PEX ID (mm, typical)Max flow @1.5 m/s copper (L/min)
15mm13.611.613.1
22mm20.217.628.8
28mm26.222.648.5
35mm32.6—75.1